At the request of the Belgian firm RDR Infra, Leak Control Benelux located the leak in an underground drainpipe.
Situation:
The site consists of 5 lots where new homes will be built. Because there is a height difference, a drainage system has been installed so that the waste water can be drained towards the main drain (main road) with the help of pumps.
Leak detection process
After the installation of the underground pipe, a pressure test revealed that there was a leak. At that time the pipeline was already buried at a depth of about 50cm (stabilisation).
RDR Infra has contacted us to urgently detect the leak without having to excavate the pipe.
Our solution:
The pipe is filled with the safe and cheap forming gas and pressurized to 8 bar (test pressure). After 1 hour the pressure dropped to 7 bar. With our Sensistor leak detection equipment connected to the optional ground probe, we have completed the trajectory (At ground level above the pipe). Within 15 minutes the location of the leak was found. After excavation it turned out to be a leaking flange.
Excavate leak location
Leaking flange connection.